PC & Devices

Battery Runtime Calculator

Estimate operating time from battery energy in Wh, average device load in W and a chosen usable-capacity percentage. These entered values define a model. The page does not measure the battery or the device's power consumption.

Use the Tool

Your Inputs

Use a decimal point, without thousands separators. Initial values are arithmetic examples. Replace them with your own data.

Your Result

Model runtime
8 h
Selected usable energy
40 Wh

The link contains input values. Anyone with it can read them. Share only what you intend to disclose.

How to Use This Tool

  1. Enter the battery capacity in Wh from a documented rating or reading.
  2. Enter a representative average load in W, not the charger rating.
  3. Choose a usable-capacity percentage above zero and up to 100, then read the estimated hours.

Calculation Method

Usable energy = capacity Wh × usable percentage ÷ 100. Model runtime in hours = usable energy Wh ÷ average load W. The percentage represents your chosen available-energy assumption; no universal loss factor is inserted.

Battery energy, usable energy and average device load connected to a runtime result.
Wh divided by W gives model hours. The usable fraction is an explicit input.

Worked Example

A 50 Wh battery with 80% usable energy provides 40 Wh in this model. At an average 5 W load, 40 ÷ 5 = 8 hours. These are illustrative inputs, not a device benchmark.

In this explanation

Choose the Energy Being Counted

The Wh input represents the capacity basis used for this estimate. A new battery's design rating, a current full-charge estimate and a remaining-energy reading are different amounts. Pick one and record its source. When using a current full-charge value, do not reduce it again for the same capacity decline. When using already-delivered usable energy, do not apply the same conversion loss twice.

A battery label or a clearly identified device report can supply energy information. Confirm its unit rather than guessing from the number's size or a field name. A confirmed 50000 mWh equals 50 Wh. A 5000 mAh charge rating is not 5 Wh. This page does not inspect the battery, upload a report or measure its stored energy. Unavailable capacity remains an unknown input, not a reason to use the example as your device specification.

Convert Charge Units Only with Matching Voltage

Wh and mAh describe different quantities. A documented charge rating can be converted outside this form using Wh = mAh ÷ 1000 × nominal battery voltage. Both figures must describe the same cell or pack and rating basis. A hypothetical 10000 mAh at a documented 3.7 V is 37 Wh. Do not multiply that charge figure by a separate 5 V USB-output label or guess voltage from the device category.

There is no voltage field or automatic mAh conversion here. Prefer a documented Wh value when available. Comparing two mAh labels without matching voltage does not establish equal energy. Likewise, a power station's advertised energy does not prove that its connector, inverter or battery can supply a particular load. Output and startup requirements need the manufacturer's separate specifications; the duration model checks none of them.

Use a Representative Average Load

Average W describes the rate of energy use for the session being planned. Match brightness, applications, peripherals, power mode and active or sleep periods to that session. A charger maximum, processor TDP or one instantaneous reading is not automatically the average battery demand. A longer observation under a comparable workload is more useful than a short reading taken during an unrelated task.

An observed 12 Wh used over two hours corresponds to 6 W on that energy-reporting basis. Equal two-hour periods at 4 W and 8 W also average 6 W. Unequal periods need a time-weighted average: sum each power × its duration, then divide by total time. Using that average in a future estimate assumes the workload pattern continues. The tool does not measure power or build the average for you.

Define the Usable Percentage Once

Enter 80 for 80%, not 0.8. The field selects a fraction of the entered energy with no hidden loss factor. Starting from a current full-charge basis, a chosen 70% to 20% window uses 50%, an approximate energy-window assumption. There are no separate charge or reserve controls. Combine the assumptions before entry and note what the percentage includes.

With 50 Wh design energy, an assumed 80% current capacity and a 60-percentage-point window combine as 0.80 × 0.60 = 0.48: enter 48%. Alternatively, use a corresponding 40 Wh full-charge value and 60%. Both select 24 Wh. Do not apply the capacity decline in both inputs. The initial 80% is an example, not universal efficiency, a health threshold or a recommended charge limit.

Read Usable Energy Before Duration

Usable Wh = entered Wh × usable percent ÷ 100. Hours = usable Wh ÷ average W. The default 50 Wh, 80% and 5 W selects 40 Wh and returns eight hours. At the same energy and fraction, 10 W returns four hours. The table compares explicit assumptions, not measured device benchmarks. More displayed digits do not make uncertain inputs more precise.

Fractional hours need conversion: 48 Wh divided by 20 W is 2.4 hours, or two hours 24 minutes. It is not two hours 40 minutes. The form displays a duration, but it does not promise the charge remaining at the end. Rate-dependent capacity, cutoff behavior, changing consumption and conversion losses can alter actual operation. A fixed fraction cannot independently predict each effect as load changes.

Same energy with different average demands
Capacity WhUsable %Average WSelected WhHours
50805408
508010404
608020482.4

Investigate a Mismatch with Observed Runtime

First check Wh versus mWh or mAh, the percentage entry, capacity basis and whether the demand is representative. Match the measurement boundary: battery-side draw already includes relevant losses, while output-side demand may need a documented delivered-energy assumption. Do not deduct those losses twice. Repeat comparable observations before attributing a shorter run to a faulty battery; workload or reporting changes can produce the same discrepancy.

Positive energy, positive average power and a usable percentage above zero through 100 are required. Zero load does not produce an infinite-runtime claim. For declining reported capacity, the separate manual ratio tool checks comparable reported numbers without diagnosing a battery. For adding energy over a charge interval, use charging time with its own effective average-power assumption. Neither replaces a device's current operating or charging estimate.

What the Result Means

Actual load changes with brightness, applications and background work. Available energy also varies. Entered averages and allowances determine the result; it does not establish guaranteed runtime or diagnose a battery fault.

Common Questions

Can I Enter mAh as Wh?

No. mAh describes charge, while Wh describes energy. Use a documented Wh value. This version does not convert mAh using an assumed voltage.

Is Charger Wattage the Device Load?

No. A charger rating does not measure the device's average demand during battery operation. Use a representative documented or measured load.